12/8/2014 5:44 AM | |
Posts: 1064 Rating:
|
simple answer 126 nodes |
12/8/2014 6:23 AM | |
Joined: 4/20/2007 Last visit: 5/27/2024 Posts: 724 Rating:
|
Up to 32 devices per segment. Up to 9 segments. Up to 126 devices. |
This contribution was helpful to
1 thankful Users |
12/8/2014 6:57 AM | |
Joined: 10/7/2005 Last visit: 6/16/2024 Posts: 3008 Rating:
|
Ok, allow me toclarify one thing here: You can have more than 9 Segments in a Profibus Network even with Siemens Repeaters. The"9 limit" only means that you can NOT place more than 9 Siemens Repeatersin series (downstream of each other). If you on the other hand use for example a PROCENTEC B1 Repeater, you'll have unlimited cascading depth and can place as many as you like in series. |
Cheers |
|
This contribution was helpful to
2 thankful Users |
6/29/2015 3:16 PM | |
Joined: 9/3/2014 Last visit: 3/13/2019 Posts: 4770 Rating:
|
|