Hello Jens_ |
11/22/2013 10:54 AM | |
Posts: 1368 Rating: (126) |
Hi Jens_ in this case, you have to use the data record 0x802A to get the current port settings of a PROFINET device. In the manual of the SCALANCE, the record is described (chapter 7.5.3) http://support.automation.siemens.com/WW/view/de/63203259/0/en Greetings, Pittiplatsch |
11/22/2013 11:15 AM | |
Posts: 1368 Rating: (126) |
You can post your project... |
11/22/2013 11:27 AM | |
Posts: 39 Rating: (1) |
Thanks!! Look at FB1 and nework 5-8. The project is done in TIA V12 SP1 update 2, can you open that ? AttachmentNetwork Test 1.zip (328 Downloads) |