Maybe you should put value 1 in mode input. |
This contribution was helpful to1 thankful Users |
4/17/2020 7:30 AM | |
Joined: 2/26/2019 Last visit: 1/19/2021 Posts: 1 Rating: (0) |
Hello, the problem is that the instant DB of MB_Master must be used with MB_COMM_LOAD's instant DB. |
9/18/2024 12:32 AM | |
Joined: 9/18/2024 Last visit: 9/19/2024 Posts: 1 Rating: (0) |
Great! Thanks you so much. |