Hello layudhi Profibus termination is an "active" termination and requires power to be effective. If you loose power to the Repeater, you will loose the termination which can then affect/disturb the Segment on which the CPU and the other DP Slaves are (and explain your problem). Possible Solutions: 1.) Use an active terminator (and make sure you don't loose power to it) instead of theRepeaters inbuilt terminator. 2.) Move the repeater from the end toa "middle" point of themain Segment I hope this helps |
Cheers |
|
1/15/2012 11:34 PM | |
Posts: 60 Rating: (1) |
Thank you very much Regards, laYudhi |