Joined: 5/12/2006 Last visit: 9/20/2024 Posts: 22365 Rating: (3011) |
Helo, connect the PLC and HMI with ethernet cable to the switrch, power on the switch, that's all.
Christoph |
1/13/2020 2:27 PM | |
Posts: 2 Rating: (0) |
Does SWITCH need settings and addressing? |
1/13/2020 3:08 PM | |
Joined: 9/27/2006 Last visit: 9/22/2024 Posts: 12282 Rating: (2684) |
Hello mehran; An unmanaged switch does not require settings or parameterization. A managed switch requires settings; these will vary in complexity depending on the functions and features you configure it for. https://www.fieldengineer.com/blogs/network-switch-managed-vs-unmanaged You can connect your PLC and HMI with an unmanaged switch, in your project, unless you have for example a redundant ring topology. Hope this helps, Daniel Chartier |
This contribution was helpful to2 thankful Users |