(0)| 7/24/2015 8:40 AM | |
|
Posts: 5521 Rating:
|
hi Allen, 1. yes you can. You can parametrize each channel-group for its own. you also have an own measure range module for each channel-group. 2. you don´t need the ext. compensation by 2-wire transducers, like you can see in the manual, chapter 6.7. Be sure that you really have a 2-wire-transducer. If it has an external power supply, you probably have a 4-wire-transducer. Therefore you should use the external compensation. Be sure that the compensation i grounded(functional ground). hope this helps, regards, |
| 7/26/2015 7:58 AM | |
|
Posts: 36 Rating:
|
Hi mopS04. AttachmentWiring Diagram.pdf (566 Downloads) |
| 11/8/2017 10:22 AM | |
|
Posts: 8171 Rating:
|
New question published by neO0O is split to a separate thread with the subject S7-300 redundant signal. Best regards |