Dear eng_semsem. Thanks your share. But when i try connect S7200 PLC to VFD022C43A, it not work. PLC Error Code 6 and Inveter Code 10 (Time response error). I use port 1 of PLC and RJ45 port in VFD (it right?) Please help me
---------------------------------------------------------------------------------------------------- |
Last edited by: Min_Moderator at: 8/7/2015 2:38:57 PMNew subject after splitting |
|
| 8/10/2015 2:33 PM | |
|
Posts: 4758 Rating:
|
|
| 8/13/2015 9:11 AM | |
|
Posts: 4 Rating:
|
Thank your response I use the programme you post, just change the Slave (4), and baudrate (9600). INVT parametter: 09-00: 4 09-01: 9600 09-02: 0 09-03: 1 09-04: 12 I afraid of the physical connection. I connect port 1 PLC with the RJ 45 of INVT: PLC(3)-INVT(3); PLC(8)-INVT(4). AttachmentDelta.rar (465 Downloads) |