(2)| 2/1/2016 1:58 PM | |
|
Posts: 5521 Rating:
|
hi dino, Do you have a fail-safe PLC in that project? If you want to use failsafe components you also need a F-CPU. regards, |
| 4/4/2016 2:19 PM | |
|
Posts: 6 Rating:
|
We also tried to create a project with an non-Siemens fail-safe CPU together with ET200M HF (153-2BA02-0XB0). My try was using the product GSD file on the non-Siemens programming tool, and, for my surprise, none of the Siemens FS-IOs (SM 326 and SM336 series) was NOT included in this GSD. By opening the GSD file with a text editor, I confirmed that my modules were not listed on the GSD. Can't understand how those devices achieved the PROFIsafe certification... |