hello IM TRYING TO CONFIGURE g120 CU240E-2 PN WITH TIA PORTAL. THE PROBLEM IS THAT I CANT CHANGE THE OPEN LOOP CLOSED/LOOP CONTROL TYPE TO PARABOLIC CHARACTERICTIC OR TO ANYTHING ELSE, ITS STUCK ON SPEED CONTRO(20). ------------------------------------------------------------------------------------------ |
Last edited by: idop at: 2/19/2017 6:29:42 AMLast edited by: Min_Moderator at: 2/20/2017 10:59:47 AMNew subject after splitting |
|
| 2/20/2017 7:38 AM | |
|
Joined: 3/31/2015 Last visit: 11/13/2025 Posts: 175 Rating:
|
Please make sure that the application type p0096 is set to 'Expert' and not 'Dynamic Drive Control' |