(0)| 8/16/2017 2:15 PM | |
|
Posts: 5521 Rating:
|
hi jack_Iohana, when you want to communicate over Profibus, you need a GSD-file, that you that is embedded to the HW-config of your DP-master. regards,
|
| 8/16/2017 8:09 PM | |
|
Joined: 9/27/2006 Last visit: 1/13/2026 Posts: 12480 Rating:
|
Hello Jack; Look at chapter 4 of the following manual, it explains the selection of the Profibus interface in DIGSI 4, and the use of the gsd file and mapping selection to integrate the Siprotec relay as a DP slave in Step 7. SIPROTEC4 - Communication module - SiemensOf course, this configuration will work if you have a PSE module (Profibus-DP interface, RS-485) installed correctly on the rear of the relay: SIPROTEC4 - Communication module - Download center - SiemensHope this helps, Daniel Chartier |
Last edited by: dchartier at: 8/16/2017 8:44:14 PMLast edited by: dchartier at: 8/16/2017 8:45:11 PM |
|