(1)| 8/22/2017 12:35 PM | |
|
Joined: 5/12/2006 Last visit: 12/19/2025 Posts: 22816 Rating:
|
Hello, which Powermodule do you use? Christoph |
| 8/22/2017 12:40 PM | |
|
Posts: 38 Rating:
|
6SL3210-1PE16-1AL1, SINAMICS POWER MODULE PM240-2 DCN, DCP, R2 terminals are not connected. |
Last edited by: The Troodon at: 8/22/2017 12:41:06 PM |
|
| 8/23/2017 7:15 AM | |
|
Posts: 38 Rating:
|
That is exactly what the problem was. 1 phase was missing. Thank you. |