(1)| 10/23/2017 1:48 PM | |
|
Posts: 37 Rating:
|
me also facing same problem...? ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 10/23/2017 2:51:32 PMNew subject after splitting |
|
| 10/23/2017 3:52 PM | |
|
Posts: 57 Rating:
|
Hi naseemk123, What you need to do is map you bool alarms in to a WORD tag, then use this tag in your HMIs alarms. Create your alarms reassembling the bools in your PLC. Use the word tag in the field 'Trigger tag' and adjust 'Trigger bit' in accordance with your mapping.
|
This contribution was helpful to
|
|
| 10/25/2017 8:16 AM | |
|
Posts: 37 Rating:
|
|
| 10/25/2017 9:09 AM | |
|
Posts: 57 Rating:
|
Using sliced addresses is probably the easiest way to do it. Just use Data Blocks instead of global memory (which was used in example) - see screenshot attached.
|
This contribution was helpful to
|
|
| 10/25/2017 10:55 AM | |
|
Posts: 37 Rating:
|
Thanks Robert_j could you explain step by step procedure for sliced address..? i just created data block named word_1 and 3 bool tags is i am on right track..? pls find the attachement
|
| 10/25/2017 12:02 PM | |
|
Posts: 57 Rating:
|
More like this: see screenshot
|
This contribution was helpful to
|
|
| 10/25/2017 1:46 PM | |
|
Posts: 37 Rating:
|
robert_j Thanks so much its resolved
|