Hi , would you mind tell me how we can communicate with MCC motor center with profinet on simicode module and read information and send command for them ? ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 11/27/2017 7:55:27 AMNew subject after splitting |
|
11/25/2017 10:17 PM | |
Joined: 9/27/2006 Last visit: 10/17/2024 Posts: 12289 Rating: (2687) |
Hello control system; The easiest way to exchnage data over Profinet between a siemens PLC and a Simocode Pro is to use cyclic data exchanges. For that you use "Basic Types", which are telegram structures that allow you to send and receive nits and analog words that allow you to control the various functions configured on the Simocode pro. Look at these documents, a basic example thread, and the System manual for Simocode Pro on Profinet: https://support.industry.siemens.com/cs/ww/en/view/61896631 Hope this helps, Daniel Chartier |