(2)| 1/19/2018 6:09 PM | |
|
Joined: 5/4/2016 Last visit: 12/17/2025 Posts: 18 Rating:
|
Most probably the actuators have different versions and the ones that are not working do not correspond with the ETS device profile version. See table attached from the datasheet p. 2 'Software versions'. The different device profiles contain a different amount of parameters due to changes. When you are using the wrong device profile, ETS is trying to write to a storage area that does not exist on the actuator. You can find the actuator version as follows: You can find and change the device profile version as follows: The latest device profile versions are available here (just sort by the product you need): Kind Regards. |
| 1/19/2018 10:56 PM | |
|
Posts: 8 Rating:
|
I see, thank you for the answer. If i update the application program with the older version, does the grop adressening and link still be ok? |