(0)| 12/11/2018 8:49 AM | |
|
Posts: 7 Rating:
|
Hello, I have a same problem. I create a connection between PLC and PC and everything is fine. When I disconnect the PC and connect PLC to the printer nothing send to the printer. In fact I want to connect the PLC to domino printer using CPU 1500. Can Someone help me? ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 12/11/2018 10:41:41 AMNew subject after splitting |
|
| 12/11/2018 11:32 AM | |
|
Joined: 7/9/2015 Last visit: 12/17/2025 Posts: 4493 Rating:
|
Hi, do you use intern PN interface of PLC 1500? Then you use the T-Blocks. These blocks have output parameters like Error / Status - please check/save Status when Error gets true. If you use S7-1500 you don´t need to use TCON - please check this: How you configure a connection in the TIA Portal?Regards, Towome |
|
|
|
This contribution was helpful to
|
|
| 7/2/2019 9:59 AM | |
|
Posts: 3093 Rating:
|
Hello, How do you evaluate the status of system blocks in STEP 7 (TIA Portal)? Does the printer use an unspecified connection? Regards, |
| 7/2/2019 10:42 AM | |
|
Posts: 7 Rating:
|
thank you for your answer. PLC is active and Printer is Passive. But still connection is not established. please see the attachment. Best Amin |
| 8/27/2019 1:11 PM | |
|
Posts: 2 Rating:
|
Hi, we have a tool, to easily connect OPC UA to Domino. So you could bridge the OPC UA Server from the S7-1500 to your printer. See a screenshot here: OPC UA <-> Domino br inray
|