(2)| 10/14/2019 9:08 AM | |
|
Joined: 5/3/2017 Last visit: 12/5/2025 Posts: 673 Rating:
|
Hello Dmitry Anyushin, you can't use CPUs with different firmware as H-System. For a H-System you have to use the identical CPUs (thats include the firmware). See the manual SIMATIC Fault-tolerant systems S7-400H at section 3.2 Rules for the assembly of fault-tolerant stations. So you have to update the firmware of the old controller. With regards |
This contribution was helpful to
|
|
| 10/14/2019 9:17 AM | |
|
Posts: 32 Rating:
|
Thank you very much! |