1/13/2020 6:24 PM | |
Joined: 12/21/2019 Last visit: 8/9/2024 Posts: 19 Rating: (0) |
I worked on your parameter , and in auto I got response from drive but the drive is not running when giving the run command on it. Drive is communicating with USS communication. but it is not giving run command to drive. ------------------------------------------------------------------------------------------ |
Last edited by: pranav7 at: 01/13/2020 19:15:06Last edited by: pranav7 at: 01/13/2020 19:15:55Last edited by: Jen_Moderator at: 01/14/2020 06:04:06New subject after splitting Thanks, |
|
1/14/2020 6:48 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877) |
Hello, Have you read & followed reply by Expert Graeme? Have you set p700 value correctly? In remote mode how you want to control drive i.e. via BOP USS link or via USS com link? Have you set BICO signals correctly? Please check. |
1/16/2020 12:30 PM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877) |
What is the status of control word 1 r0054 when you applied run command? |