4/3/2020 7:59 AM | |
Joined: 7/7/2015 Last visit: 7/31/2024 Posts: 17 Rating: (0) |
Hi guys, is there anyway to deploy running hours function in ABT pro with DXR2 ? I have a require from customer who like to monitor fan running hours in room. ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 04/03/2020 11:33:22New subject after splitting |
|
4/15/2020 9:20 AM | |
Joined: 6/25/2013 Last visit: 3/20/2024 Posts: 13 Rating: (13) |
Hi Triet I made a small solution to count the operating hours (see attachment) of a status object. The status value is read in and starts the counting up every minute. The resulting value is then written to a BACnet object. The value stays also in a case of a power fail of the DXR2. AttachmentOperatingHourCounter_Triet.docx (459 Downloads) |
This contribution was helpful to1 thankful Users |