Hello, it is not possible to change the alarm reaction. It would be possible to override Bit 1 (Off2 ; Bit1 := True;) of the control word in MC_PostServo, to avoid a cost stop or you can monitor for your own, and do a stop when position deviation becomes too big. General Info: Drive Connection via PROFIdrive https://support.industry.siemens.com/cs/ww/en/view/109770665 |
|