Hi Thompsonvk I have 1 s7-1200 and 1 s7-300 plc. I connected and communicated 2 plc and wincc pro. I took db503.dbw24 values from S7-300 plc to wincc pro. Its okay. But my question is that, how i can use this value in s7-1200 plc like normal contact or output. I must not use s7-300 because of risk that for me. Could you please inform me documentation or videos etc? My mail adress: [snip] I am waiting your reply. Thanks ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 02/26/2021 13:45:06New subject after splitting. Removed E-Mail address. |
|
| 2/26/2021 4:01 PM | |
|
Joined: 7/7/2010 Last visit: 1/7/2026 Posts: 16354 Rating:
|
In the S7-1200, configure the S7-300's profinet subnet for it's PN/IE so they can communicate. Then in the S7-1200, drag in the S7 GET instruction. Read up on the parameters, and configuration options. Use the configuration icon after inserting the block to create the partner (S7-300) connection by inserting its IP address. Hope this helps.
|
|
science guy |
|
| 2/26/2021 8:27 PM | |
|
Joined: 9/10/2019 Last visit: 9/30/2025 Posts: 30 Rating:
|
thanks So you used script of scada? Like that set tag or get tag Can I use this script? |
| 2/26/2021 8:56 PM | |
|
Joined: 9/10/2019 Last visit: 9/30/2025 Posts: 30 Rating:
|
Can I use script for tranfer data s7-1200? I looked set tag and get tag. Do you have experience about them? |