(0)| 2/8/2012 11:02 PM | |
|
Joined: 7/16/2008 Last visit: 2/28/2025 Posts: 17 Rating:
|
Hi Bouncer12 How exactly did you check the profibus cables? Have you use multimeters to check terminators resistance? Do you use terminators on connectors or external active terminators? Do you use profibus repeaters in your network? If you have one spare you can install it somewhere in the middle on your network to amplify and form signal. What is bus speed? You can try to slow it down to make communication more distortions resistant. regards, goblin |
| 2/9/2012 9:21 AM | |
|
Posts: 4 Rating:
|
the fault appeared about 48 hrs ago it took us whole night to aknowledge the fault .After a struggle of more than 8 hours we were able to identify a faulty bus connector and the fault was aknowledged the machine ran smothly for 48 hours and than again this morning the fault appeared bring the line to a halt but this time the fault appeared only on one perticular TB we have replace the connecter of the Tb and aknowledged the fault but still the exact caiuse of the fault is not yet identified. In context to Mr.goblinyes the system has repaeaters .we have replaced the profibus b/w the stattions at which the fault appeared more frequently but was still were not able to cure the fault . We checked the health of the connector witht he help of multimeters by turning the Terminating resistance on and off.A couple of them were found faulty we replaced them with healty ones.... As for checking the healt of the whole profibus cable kindly do suggest a methhod using multimeter to check it Thanks
|
| 2/13/2012 1:47 PM | |
|
Posts: 4 Rating:
|
Can any one plz tell me the method of checking profibus with the help of a multi meter or Using PG |