Well, This is not Auto Reset problem so dont go for it Now, i have seen same things in few cases. Things to check - P640- Your current Limit, r0027 Actual current What control mode is selected? If it is V/F ( P1300=0), try to go for SLVC (P1300=20) For this, you need to do optimization also to get good result (P1910 & P1960) Refere Manuals - Operating Instruction and Parameter List Regards, Devesh Vithani |