(0)| 9/6/2012 10:04 AM | |
|
Joined: 4/22/2010 Last visit: 3/31/2025 Posts: 5697 Rating:
|
Thatmust bethe problem, you should use MPI cable or Profibus cable with profibus connectors. Use the RS485 port on the panel. The 200 PLC has no RS232 port. Have a look at What should you watch out for when setting up a connection between S7-200 and SIMATIC Panels or WinCC flexible PC Runtime and what are the options? Regards, Marcjan |
Last edited by: Marcjan at: 9/6/2012 10:11 AMProblem solved? |
|
| 9/6/2012 11:26 AM | |
|
Joined: 4/22/2010 Last visit: 3/31/2025 Posts: 5697 Rating:
|
Hello, You can find the manual here You should start with checking communication settings on panel and in the S7-200. If the system had worked before what actions did you make? Regards, Marcjan |
|
Problem solved? |
|
| 9/7/2012 4:47 AM | |
|
Posts: 4 Rating:
|
Thanks for the manual link. By this i can check the communication setting in the OP77B panel, but how to check the setting in the S7-200 PLC? Thanks in advance. |
| 4/25/2016 12:14 PM | |
|
Posts: 4758 Rating:
|
New question published by Azeezbolly is split to a separate thread with the subject OP77B communication with S7-200 PLC problem. Best regards |