(0)| 12/29/2012 12:27 PM | |
|
Posts: 1410 Rating:
|
BF= Bus Failure You don't have a slave device connected (or improper configurated) on profibus network. |
| 12/29/2012 6:19 PM | |
|
Joined: 3/21/2006 Last visit: 10/16/2025 Posts: 10239 Rating:
|
To add there - in diagnostic buffer you can see which addresses are not 'online'. |
| 3/16/2017 4:54 AM | |
|
Posts: 2 Rating:
|
Hi Dear all, I also facing the same problem on S7 cpu315 2pn/dp bf1 blinking and sf led onplease help me how to clear it and solve . attached is my Diagnosis Buffer , FYR. AttachmentDiagnose.txt (655 Downloads) |
| 3/16/2017 4:56 AM | |
|
Posts: 2 Rating:
|
all function is OK and hardware configuration also no red link .Thanks |
| 3/16/2017 7:28 AM | |
|
Posts: 5521 Rating:
|
hi, BF1 LED indicates a problem on the Profibus. Please show us a screenshot from your HW-config online. regards, |