Sorry Niranjan, but in most cases you can modify hw config while keeping the system running. You see the chapter 14 of the Fault taulerant systemmanual. (edition 5/2008) In brief,
Now remember that during this switchover the PIP image is "frozen", so make sure nothing high speed and very critical is running. |