Hello Bertus@NBL, you need the SIWATOOL for configuration the WP231, please look at this document: Hope it helps. |
| 8/26/2016 10:14 AM | |
|
Joined: 1/4/2007 Last visit: 12/16/2025 Posts: 1197 Rating:
|
Hello Bertus@NBL, Unfortunately CaOd is not right. It’s not necessary to use the Siwatool software to configure the WP231 module. You can find an example project on the internet (file: “ready_for_use_modbus.zip”): With this example project you can connect a TP700 HMI-panel directly to the WP231 module and you configure the WP231 module via the TP700. If you change the IP-address of the WP231 module, you also have to change the partner-IP-address of the HMI-panel (= IP-address of the WP231 module) into the TIA Portal software.
|
This contribution was helpful to
|
|
| 8/29/2017 1:44 PM | |
|
Joined: 8/21/2014 Last visit: 12/19/2025 Posts: 1098 Rating:
|
New question published by msgsadek is split to a separate thread with the subject Can you guide me if i want to use KTP1200 BASIC instead of TP700 ??. Best regards |
|