i have siemens 802d system im facing one problem when i giving cammand to sp is rotating but with 2 sec below alarm occured 207410 axis sp drive 1 drive current controller output limited please guide ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 09/02/2019 07:09:40New subject after splitting |
|
9/1/2019 8:48 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877)
|
Hello ket2, You should have post this query in SINUMERIK CNC automation systems product conference. F207410 - Actual current drawn by motor is zero when quadrature voltage set point 1 is set. So check your spindle motor connection, DC bus voltage at r0070, or check spindle motor cable & winding resistance. If everything is ok, then S120 Motor module might be faulty, replace it & check. HTH. |