1/15/2021 10:54 AM | |
Joined: 5/16/2014 Last visit: 9/12/2022 Posts: 7298 Rating: (2145)
|
Hello K. Sunny, the Alarm-Control-Table is limmited for showing see manual "SIMATIC HMI WinCC V7.5 SP1 WinCC Information System" https://support.industry.siemens.com/cs/ww/en/view/109772961/111335874443 Regards Georg Berghof |
PS: If this post did really help you, you may use the Rate-button |
|
1/15/2021 10:56 AM | |
Joined: 2/6/2015 Last visit: 4/19/2024 Posts: 80 Rating: (15) |
Hi K. Sunny, This is normal. Alarm control can only show up to 1000 Alarms. See this FAQ: Why are only 1000 messages shown in the archive window although there are more in the archive? https://support.industry.siemens.com/cs/ww/en/view/1957448 Best Regards, CGA81 |
If this Information really helps, you could use the Rate function |
|