8/25/2014 6:19 AM | |
Joined: 1/21/2013 Last visit: 9/4/2024 Posts: 4620 Rating: (707) |
Hi cy429, First you need to bring the green LED Fixed, then you used the FC14 in your program? The CPU is in RUN? Show some message your BOP mounted on the Micromaster (e.g. A0703)? I've attached the user manual of the Profibus module that you have installed on your Micromaster, as you can see in Chapter 7, the flashing green LED means: Manual wrote Led flashing green: Cyclical process data exchange in progress, but setpoints invalid (control word = 0), e.g. because SIMATIC master is in "Stop" state Look chapter 7: Operating Instructions: MICROMASTER PROFIBUS Optional Board |
Last edited by: Ste39 at: 8/25/2014 7:06 AMAlarm number (maybe) |
|
8/30/2014 8:42 PM | |
Joined: 1/21/2013 Last visit: 9/4/2024 Posts: 4620 Rating: (707) |
Hello cy429, Have you solved your problem?
|