hello, Please take care that the input and output addresses of Simocode in HW-Config are identical. Furthermore the Simocode “DP interrupt mode” has to be “DPV1”.That’s all what has to be considered from Simocode side. If there are still problems the firmware of the Y-Link would be very helpful. Or send your project to: technical-assistance@siemens.com kind regards |
12/3/2016 8:24 PM | |
Posts: 3 Rating: (0) |
Hi Dear. Did you found the solution to this issue? I have the same problema and could fix it yet? |