Joined: 9/27/2006 Last visit: 9/22/2024 Posts: 12282 Rating: (2685) |
Hello DavinO; To sync the tags between the redundant controllers and the WinCC application, you need to create a redundant connection in WinCC, attached to both of the S7-300 CPUs. This is described in the SWR manual: SIMATIC S7-300/S7-400 Software redundancy for SIMATIC S7 https://support.industry.siemens.com/cs/ww/en/view/1137637 in Chapter 9: "Software redundancy and operator stations with WinCC" They refer to an additional document “SWR_WinCC_English.pdf” tht can be found in this thread, posted by S7Automan: S7-300 Software Redundancy Switch over sequences not switch over all output switch off Hope this helps, Daniel Chartier |
9/19/2020 5:47 PM | |
Joined: 2/16/2020 Last visit: 9/20/2024 Posts: 26 Rating: (0) |
Thank you very much for your reply - You can share the example mentioned in the document
|
9/20/2020 3:34 PM | |
Joined: 2/16/2020 Last visit: 9/20/2024 Posts: 26 Rating: (0) |
Thank you very much Daniel - |