8/27/2015 8:09 AM | |
Posts: 1 Rating: (0) |
hello sir, iam having problem reading total kilowatt reading from sentron pac3200 energy meter.its shown in manual offset address 65 and no. of registers 2.Since iam using modbus rtu protocol i used 400066 to read the value.Should i use the next register i.e. 400067? ------------------------------------------------------------------------------------------ |
Last edited by: Min_Moderator at: 8/27/2015 1:17:28 PMNew subject after splitting |
|
1/26/2022 8:52 PM | |
Joined: 3/25/2021 Last visit: 1/26/2022 Posts: 1 Rating: (0) |
I believe you have one too many 0 - 40066 is the kW total |