Sorry! Ask to add a question Modbus RTU Mag 6000 Now I Can Link and recieved the value. but The value does not match betaween Mag6000 and PLC. In case ! What should I do. ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 4/11/2019 12:04:36 PMNew subject after splitting |
|
4/12/2019 7:22 AM | |
Posts: 14 Rating: (0) |
good day! I sent the picture to see how it can be converted to match. |
4/12/2019 9:09 AM | |
Posts: 1283 Rating: (105) |
what value you are getting in 3022 register? |
4/12/2019 9:31 AM | |
Posts: 14 Rating: (0) |
The value move around. |
4/12/2019 10:00 AM | |
Posts: 14 Rating: (0) |
Attachmentmod.avi (324 Downloads) |
4/12/2019 10:12 AM | |
Joined: 12/18/2014 Last visit: 9/22/2024 Posts: 33816 Rating: (4201) |
On your screenshots, is this a Modbus simulator? Which PLC are you using? |
4/12/2019 11:23 AM | |
Joined: 12/18/2014 Last visit: 9/22/2024 Posts: 33816 Rating: (4201) |
What data type ist the 8 Byte value? LINT? that's no the same as double float. |
4/12/2019 11:35 AM | |
Posts: 14 Rating: (0) |
LREAL! |