5/14/2012 10:19 AM | |
Joined: 9/28/2005 Last visit: 8/27/2024 Posts: 2957 Rating: (242)
|
If you make L MW1 then: MB1 is byte 1 MB2 is byte 0 If you make L MD1 then: MB1 is byte 3 MB2 is byte 2 MB3 is byte 1 MB4 is byte 0 Best way to understand is to execute those command on real PLC and see in VAT table what you have. Siemens use big endian architecture, so I hope moderators will not mind by inserting external link here http://en.wikipedia.org/wiki/File:Endianessmap.svg |
Best regards, |
|
This contribution was helpful to1 thankful Users |
5/14/2012 10:28 AM | |
Joined: 5/1/2009 Last visit: 5/23/2021 Posts: 144 Rating: (1) |
hello can you explain the diffrent between MD0 and MD1 ?
|
Best regard |
|