7/10/2019 6:20 PM | |
Posts: 1 Rating: (0) |
Hi, When i try to download the program to a QMX3.P30 Room Unit i recieve this error: "ETS tried to write a protected or a non existing memory block" I'm using ETS 5 with knxprod version 2.0 ... Can you help me please? Thanks Fausto ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 07/11/2019 07:02:01New subject after splitting |
|
7/11/2019 7:40 AM | |
Joined: 6/4/2010 Last visit: 9/18/2024 Posts: 387 Rating: (128)
|
Dear Fausto, You may have an older QMX3 version. Please check the manufacturing date on the device. You need to use the old product data base file (VD file) in case the device has a manufacturing date before July 2015. You can find the old product description files under the link below: https://www.hqs.sbt.siemens.com/cps_product_data/data/search_find_en.htm Please search for the QMX3 and selected the “archived” files on the right upper corner. See attached print screen. Best regards, Albis |
Last edited by: Albis at: 07/11/2019 07:43:33 |
|