8/19/2015 11:46 AM | |
Posts: 739 Rating: (55)
|
please try P0700=4 see also: https://support.industry.siemens.com/cs/ww/de/view/10556575/en |
Last edited by: JensS at: 8/19/2015 11:48:03 AM |
|
8/21/2015 8:00 AM | |
Posts: 739 Rating: (55)
|
drive monitor appear message " no command control acceptance " The AOP sets the PZD word length to 4, while DriveMonitor and Starter by default use a word length of 2. (The PZD is part of the data message used to transmit information between the drive and AOP or PC). Therefore if Starter or DriveMonitor are used after an AOP there will be communications problems. There are several easy fixes, for example: Reset P2012 to 2 (remember index 1 sets the BOP link and index 0 the COM link) Or reset the parameters using P0970 Or simplest solution: cycle the power, as the AOP writes this value to only the RAM of the drive, and therefore P2012 will be reset to 2 if the power is cycled.
Not Available - P to Acknowledge " What is the cause of the AOP/BOP message "P----"? https://support.industry.siemens.com/cs/ww/de/view/21228857/en How should the AOP be set for reliable communication? https://support.industry.siemens.com/cs/ww/de/view/10556575/en if this don’t help, please open an Support Request (https://support.industry.siemens.com/My/ww/en/requests) our technical support will be pleased to assist you.
|
8/24/2015 11:32 AM | |
Posts: 739 Rating: (55)
|
Before you change the Battery of your AOP please read this FAQ carefully! Otherwise you can thrash the AOP!
MICROMASTER 4 (MM4): How long does the battery last in the AOP and how can it be changed if required? https://support.industry.siemens.com/cs/ww/en/view/21367554 |