hi, How is your Baud-Rate? have a look to this FAQ: Acceptable line length in PROFIBUS-DP networks hope this helps, regards, |
FCK WAR! |
|
8/25/2019 1:31 PM | |
Posts: 8 Rating: (0) |
Dear Vinoth, mopS04, Thank you for your reply. I am unable to check the baud rate at the moment, as the Profibus configuration software for the Honeywell PGM is unavailable at the moment. I need your advice on my plan. My Plan is to introduce. a) 6ES7972-0AA01-0XA0 Profibus REPEATER, inbetween Slave-2 & Slave-3(the last node). b) Also, to introduce Profibus Active Termination P/N:101-00211A at the end of Slave-3. Can you share your experience in this regards? if you have ever used it. Would it be helpful to achieve better signal strength while not altering the Baud Rate of the Loop? As always appreciate for your valuable inputs. Regards, Rajesh Kothari. |