i want to read current from sinamic G120 by using Profibus. please provide any easiest solution. ------------------------------------------------------------------------------------------ |
Last edited by: Min_Moderator at: 1/30/2017 3:32:51 PMNew subject after splitting |
|
1/31/2017 10:18 AM | |
Joined: 10/11/2006 Last visit: 8/29/2025 Posts: 6037 Rating:
|
Hello, with Profibus communication you can use telegram 20 to transfer the actual current r68[1] to the PLC. Of course you can use a “free telegram” to define the parameters which should send to the PLC freely. A good overview over the possible telegrams could be found in the G120 list manual in function diagram 2420. https://support.industry.siemens.com/cs/ww/de/view/109482961/en |