Regarding the button, I suggest using APL template, by using the APL operator button 1. Copy the APL_OP_BUTTON from @PCS7_ElementsAPL.pdl. 2. Assign a meaningfull name to your object 3. Enter your object name in the "stUser" object 4.At the OpAreaHeading property you can set three of five button operation, by using @pg_apl_oa_binary103.pdl (three) or @pg_apl_oa_binary105.pdl (five). 5. Adjust your object by using the following properties.
For the rest: I don't think you can set something in CFC block without using OCM through WinCC.. The only other way is to use a digital operation signal (OpDI) with OCM and connect the output to your block. |