(1)| 11/26/2018 7:16 PM | |
|
Posts: 3 Rating:
|
Dear Experts, I am trying to setup the data logging on demand function on Siemens Basic KTP400 panel to save the datalog to the USB memory stick. The Idea is to log data at specific moment. At first I made data log in Historical Data, with necessry tags. After I create a trigger bit in PLC. In the properties of this bit in HMI tags in Data change Event I created the "LogTag" functions for necessary tags. But the logging is not working. It is working "on change" of the value, "acyclic" also working. This mode - no. Can somebody help me? I am programming on TIA portal Version 14. Thanks a lot for your help!!! ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 11/27/2018 6:35:57 AMNew subject after splitting Last edited by: AutoGen_6037935 at: 11/27/2018 8:12:42 AM |
|
| 11/28/2018 7:32 AM | |
|
Posts: 3 Rating:
|
Thank you! Now It is Working! And It is clear for me - Why before it was Not! The simplest thing I did not know About. |
| 1/11/2021 12:23 PM | |
|
Posts: 1 Rating:
|
sorry friend where do you seting the °°cicle continuis°° im still have the same problem ( no log ) im using ktp700 basiic, usb 4gb,fat 32 |
| 7/12/2021 11:07 AM | |
|
Posts: 1 Rating:
|
You can do it in the properties of the tag itself |
This contribution was helpful to
|
|
| 12/15/2021 10:50 PM | |
|
Posts: 11 Rating:
|
Hello, you can use a variable from PLC to make visible some text, the same variable should have the events configured to trigger log system functions.
|