please i have same problem how can i reload the nc.arc and plc.arc files my unit is ccu 810d ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 10/15/2018 2:36:37 PMNew subject after splitting |
|
10/16/2018 12:45 AM | |
Joined: 10/17/2007 Last visit: 9/17/2024 Posts: 4031 Rating: (353)
|
Your 810D CCU communicated with HMI (MMC100. MMC103 or PCU20,PCU50) through MPI cable. #1--if you have MMC103 or PCU50 (both have HDD, ) your NC.arc and PLC.arc stored on the HDD. so you need input password =SUNRISE , then going to "services" menu, find NC.arc and PLC.arc, files and load them #2--iF YOU HAVE mmc100 OR PCU20, you need use extenal PC plus SW WinPCIN, to load those 2 files
|
If you like my comments please |
|
10/19/2018 2:32 AM | |
Posts: 11 Rating: (0) |
its look like this |
10/19/2018 2:43 AM | |
Posts: 11 Rating: (0) |
this is the back side for the display and not have any stander type please advice |