How would you go about running a safety commission? Thanks! |
2/13/2019 8:33 AM | |
Joined: 10/11/2006 Last visit: 9/18/2024 Posts: 5906 Rating: (804)
|
Hello, if you have selected safety integrated basic functions you have to supply 24V to terminals 16 &17 to deselect STO. Because your screenshot also shows that a lot of other enable signals are missing, I would recommend to use the STARTER control panel to provide the enable signals to see if just the safety enable is missing. You can use our application examples for information regarding safety commissioning.https://support.industry.siemens.com/cs/de/en/view/58820849 Or you can use our videos regarding safety commissioning. https://youtu.be/XuPNDyYPCN4 |