Dear Sir, I have problem on 840Dsl, alarm no is 400260 failure of machine control panel 1 can you suggest me to solve this problem. This is for your kind information and do the needful. Thanks & Regards, Radhakrishna.P
------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 06/19/2020 09:10:54New subject after splitting |
|
6/19/2020 3:31 PM | |
Joined: 10/17/2007 Last visit: 9/17/2024 Posts: 4031 Rating: (353)
|
I suppose you have in-use machine, it working good yesterday and gave you this alarm this morning. you can check the cable (MPI or Ethernet) to communicate from NCU to MCP and open the MCP back to see it have power (some led's on or flashing) possible MCP defective. attached page of this alarm from Siemens, it is always good you find Siemens Diagnostic Manual for 840D/840D sl
|