4/24/2016 11:34 AM | |
Posts: 5 Rating: (0) |
Hello, We have a use to Generator excitation system THYRIPOL . We must change generator under excitation limiter for reactive test completed. I found the parameters to be changed. How do I connect the computer to the T400 technology card ? How do I download the program in my computer 's T400 available ? Can you help me ? Thank you in advance for your help Best Regards ------------------------------------------------------------------------------------------ |
Last edited by: The Helping Hand at: 4/25/2016 9:48:23 AMNew subject after splitting |
|
4/24/2016 1:03 PM | |
Joined: 8/25/2006 Last visit: 9/23/2024 Posts: 2209 Rating: (278)
|
Hello. What order number of your T400?
If you have CFC-program for T400, then you can download it via RS232. If your T400 is with standard program you can download/upload parameters backup using DriveMonitor.
|
This contribution was helpful to2 thankful Users |
4/24/2016 3:24 PM | |
Joined: 11/21/2007 Last visit: 8/12/2024 Posts: 2325 Rating: (308) |
Hello You will need a connecting cable as described in Section 3.7.1.2. Connecting cable to the PC of attached T400 Brief Description Link for : T400 - Detailed User Manual Hope this helps Cheers Navnag AttachmentT400_Brief_Description.pdf (1070 Downloads) |
There is no such thing as the last bug in a program |
|
This contribution was helpful to1 thankful Users |
4/25/2016 2:49 PM | |
Posts: 5 Rating: (0) |
I must change generator under excitation limiter for reactive test completed. I need to change two parameters T400 card. Step vay step 1- T400 card, I connect a PC with the installed base of CFC and D7-SYS software 2- I update the program on my desktop, connecting the T400 card 3-then I'll change two parameters 4-After I download the program in T400 programs on the computer is attached I will change when you open the program parameters in section Begrenzungen Names of parameters : L131, L132, L133, L134, L135, I ask you: Can I change this way. Is any problem happens ? Thank you for helps Best Regards AttachmentSey_2_K1.zip (810 Downloads) |
4/25/2016 8:24 PM | |
Joined: 11/21/2007 Last visit: 8/12/2024 Posts: 2325 Rating: (308) |
Hello KSN New subject after splitting
I did not notice the 2nd post , this was in the context of the Original post for Rewinder. Thanks for correcting me. Cheers Navnag
|
Last edited by: Navnag at: 4/25/2016 8:51:48 PMLast edited by: Navnag at: 4/25/2016 8:52:30 PMThere is no such thing as the last bug in a program |
|
4/26/2016 10:36 AM | |
Joined: 8/25/2006 Last visit: 9/23/2024 Posts: 2209 Rating: (278)
|
Hello. I'm not a specialist of THYRIPOL system, so it will be better for you to make a support request. |
1/9/2019 7:08 AM | |
Joined: 8/25/2006 Last visit: 9/23/2024 Posts: 2209 Rating: (278)
|
Hello. If you have CFC-program for T400 on your PC, you can go online with this program. Change your usb-rs232 adapter to COM1 or COM2, use DUST1 (COM1 or COM2) in Setting the PG/PC Interface, use the cable mentioned here, open CFC-chart and go online. |
1/10/2019 5:53 AM | |
Joined: 8/25/2006 Last visit: 9/23/2024 Posts: 2209 Rating: (278)
|
Hello. Try to install Update 3 for D7-SYS V7.1 SP1, there is a note about corrections of using DUST1 in 'D7-SYS - Release History'. |