7/20/2020 10:46 AM | |
Posts: 22 Rating: (0) |
Hello, I have an S7-300 CPU 315-2 DP controller which automatically goes into stop mode following a fault with a profibus station. Is there a way for the PLC not to go into stop mode even if the fault exists. Thank you ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 07/20/2020 12:44:01New subject after splitting |
|
7/20/2020 2:09 PM | |
Posts: 22 Rating: (0) |
Thank you very much it was the OB85 missing, I created it and I loaded it hope it's the only one missing. Thank you very much Best regards |