6/17/2019 3:07 PM | |
Joined: 5/22/2012 Last visit: 3/24/2022 Posts: 895 Rating: (67) |
What is the Setting in p1300? The SINAMICS has two different VdcMaxMin Controller. One for V/f and one for p1300>= 20. |
6/18/2019 10:34 AM | |
Posts: 10 Rating: (0) |
the setting of P1300 was 0.. |
6/18/2019 11:21 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877) |
Check value in p0210, p1254 & 1294. If 1254 & 1294 = 0, set 1255 & 1295 = 1 sec. |