11/19/2021 3:30 PM | |
Joined: 10/9/2021 Last visit: 8/21/2024 Posts: 20 Rating: (0) |
Hello, I have S7-400H system in my project and I wish to communicate to 3 S7-1200 controllers. I am also trying same approach of importing gsdml given by supplier. However, i am quiet new to this. Can you explain me detailed process for such configuration? What i must do after installing S7-1200 gsdml in PCS7? What configurations in PCS7 must be done? Is there any document which explains this? Thanks in advance. ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 11/22/2021 08:57:58New subject after splitting |
|
11/22/2021 9:33 AM | |
Joined: 1/11/2019 Last visit: 9/17/2024 Posts: 758 Rating: (150) |
Hi Shree2893, The 400 and 1200 can communicate and exchange the data between them using communication blocks. The 1200 controller logic cannot be programmed in PCS 7 as it is not a part of PCS7 component. Below link/thread can help you to get the required information. How to configure S7-1200 in PCS7 Hope it helps you |