@Willybong: thats wrong. this is about Step7 classic. You´re right with S7-1500 in TIA. But with S7-300/400 your can change the view betweent the languages STL, LAD and FDB. In the CPU every block is translated to STL. For the view of LAD and FDB blocks the compiler needs instructions in STL to represent the graphics, like "BLD" or "NOP 0" have a try and write some code in LAD and change the view into STL. this is why extensive and big STL-networks can not presented in graphical languages, like LAD and FDB. Also see other topic about this subject. When you use the search function in the upper right, you will find topics like this: Why can't I change STL to LAD ???hope this helps, regards, |