Hello, the reason for the alarm 800F: The job cannot be executed because the technology object is locked. Enable the technology object with "MC_Power.Enable" = TRUE. Restart the job. • A "MC_Stop" job is active with "Execute" = TRUE. Reset the job with the parameter "Execute" = FALSE. Please check the stae of the TO, before setting MC_MoveVelocity. (<TO>.StatusWord.X0 (Enable)) (<TO>.StatusWord2.X0 (StopCommand)) 6. Diagnostics (S7-1500, S7-1500T) https://support.industry.siemens.com/cs/de/en/view/109781849 |