9/1/2017 8:38 AM | |
Joined: 2/4/2015 Last visit: 7/26/2023 Posts: 64 Rating: (0) |
Hi all, I want to know whether a SSI signal output of a LVDT can be connected to FM351 or not? Presently a hydraulic cylinder is operated via parker made Compax controller and we want to replace it with FM351 module? Is it possible? Kindly reply Regards Surendhar M +91 90400 96020 ------------------------------------------------------------------------------------------ |
Last edited by: The Helping Hand at: 9/1/2017 1:03:45 PMNew subject after splitting |
|
9/1/2017 11:19 AM | |
Joined: 3/5/2014 Last visit: 8/5/2022 Posts: 5521 Rating: (1050) |
hi, have a look to the technical data of the module you want to use: 6ES7351-1AH02-0AE0FM351 POSITIONING MOD. RAPID/CREEP FEEDfor me, it seems that it is possible, regards, |
FCK WAR! |
|